Insulated Single-screen Horizontally Fire Rated Shutter

Type: Fire Rated Shutters



Model: SIH-152 SIH-152E

Comply with BS746: Part 22: Clause 6, 1987 with 152 mins insulation and 243 mins integrity


Symmetric slat curtain system comprised of whole shutter assemblies including enclosure box, endplates, barrel, side track and slat curtain.

Specimen size 3,630 mm wide by 4,870 mm long
Laboratory
Research Engineering Development Facade Consultants Limited (RED)
Test Standard

BS476: Part 22: Clause 6, 1987


Exclusive connectors (Patent application no. PCT/CN2014/070276)

The slat curtain system is comprised of steel hollow section slat with ceramic wool infill sandwiched by ceramic blanket. Exclusive connectors (Patent application no. PCT/CN2014/070276) are used to detach the heat resisting ceramic blanket and the steel slat curtain in case of fire, terminating of heat conduction from steel slat curtain to heat resisting ceramic blanket, and vice versa. Additional fabric glass can be added to the outer layer of slat curtain for decoration. 


Two outstanding mechanisms are incorporated:


1. Barrel built with spring coil

    The tension of spring coil inside the barrel ensures slat curtain rolling around the barrel tightly when the shutter is fully opened, minimizing the size of enclosure box.


2. Curtain Holdfast Device (CHD)

    CHD is incorporated at two ends of the slat curtain, maintaining the steel curtain as straight as possible when the shutters is fully closed.



Picture 1) 

Fire side - Ceramic blanket fixed to steel slat with bi-parting junction

Non-Fire side - Ceramic blanket fixed to steel slat with bi-parting junction

Performance - 152 mins insulation & 243 mins integrity


Picture 2) 

Typical Drawing